Wire Gauge Calculator - AWG Size Reference & Specs
Science & Engineering
Look up AWG wire specifications and estimate copper voltage drop from current, run length, system voltage, and wiring phase.
| Diameter (mm / in) | 2.053 / 0.0808 |
| Cross-section area | 3.309 mm² |
| Resistance (copper, 20°C) | 5.211 Ω/km (0.005211 Ω/m) |
| Max current estimate - chassis / open air | 41 A |
| Max current estimate - in-wall / conduit | 20 A |
Voltage drop estimate
Estimate voltage loss for the selected AWG copper wire using resistance at 20°C.
Estimated voltage drop: 3.177 V
Voltage drop: 2.647% of 120 V
At or below the 3% reference for this entered wire run.
Formula: I × 5.211 Ω/km × 15.24 m ÷ 1000 × 2.
This resistance-only estimate assumes copper at 20°C. It does not model AC power factor, reactance, conductor temperature, or installation conditions. The 3% and 5% figures are informational design references; this panel estimates only the entered run and does not certify code compliance.
| AWG ▲▼ | Diameter (mm) ▲▼ | Area (mm2) ▲▼ | Ω/km ▲▼ | Max A (chassis) ▲▼ |
|---|---|---|---|---|
| 4/0 | 11.684 | 107.2 | 0.1608 | 380 |
| 3/0 | 10.405 | 85.01 | 0.2028 | 328 |
| 2/0 | 9.266 | 67.43 | 0.2557 | 283 |
| 1/0 | 8.252 | 53.48 | 0.3224 | 245 |
| 1 | 7.348 | 42.41 | 0.4066 | 211 |
| 2 | 6.544 | 33.63 | 0.5127 | 181 |
| 3 | 5.827 | 26.67 | 0.6465 | 158 |
| 4 | 5.189 | 21.15 | 0.8152 | 135 |
| 6 | 4.115 | 13.3 | 1.296 | 101 |
| 8 | 3.264 | 8.367 | 2.061 | 73 |
| 10 | 2.588 | 5.261 | 3.277 | 55 |
| 12 | 2.053 | 3.309 | 5.211 | 41 |
| 14 | 1.628 | 2.081 | 8.286 | 32 |
| 16 | 1.291 | 1.309 | 13.17 | 22 |
| 18 | 1.024 | 0.8231 | 20.95 | 16 |
| 20 | 0.8128 | 0.5189 | 33.31 | 11 |
| 22 | 0.6438 | 0.3255 | 53.46 | 7 |
| 24 | 0.5106 | 0.2047 | 84.22 | 3.5 |
| 26 | 0.4049 | 0.1288 | 133.9 | 2.2 |
| 28 | 0.3211 | 0.081 | 212.9 | 0.83 |
| 30 | 0.2546 | 0.0509 | 338.6 | 0.52 |
| 32 | 0.2019 | 0.032 | 538.3 | 0.32 |
| 34 | 0.1601 | 0.0201 | 856 | 0.18 |
| 36 | 0.127 | 0.01267 | 1361 | 0.1 |
| 40 | 0.07987 | 0.00501 | 3441 | 0.036 |
Current values are simplified reference estimates, not NEC ampacity ratings.
How to use this tool
- Select an AWG gauge from the dropdown or sortable reference table.
- Review its wire specifications and enter run details to estimate copper voltage drop.
AWG wire gauge overview
The AWG (American Wire Gauge) system uses an inverse scale - lower numbers mean thicker wire. 4/0 (0000) is the largest common gauge; AWG 40 is fine enough for watch coils.
Choosing the right gauge
- Match wire gauge to the maximum continuous current, not peak current.
- Derate by 20–30% when bundling multiple conductors.
- For long runs, consider voltage drop in addition to current capacity.
AWG to mm² conversion table
| AWG | mm² | Typical use |
|---|---|---|
| 18 AWG | 0.82 mm² | Signal wiring, low-voltage lighting |
| 14 AWG | 2.08 mm² | General lighting circuits (15 A) |
| 12 AWG | 3.31 mm² | Standard outlets (20 A) |
| 10 AWG | 5.26 mm² | Dryers, EV charging (30 A) |
| 6 AWG | 13.3 mm² | Sub-panels, large appliances (55 A) |
Voltage drop calculation
Excessive voltage drop can reduce equipment performance and cause lights to dim. NEC informational notes discuss 3% on branch circuits and 5% total (feeder + branch) as design guidance for efficiency; these are not mandatory universal limits and do not establish code compliance. This estimate uses the selected wire’s copper resistance at 20°C:
V_drop = I × R_per_km × length_km × factor
factor = 2 for DC or single-phase; √3 for balanced three-phase For example, 20 A through a 50-foot one-way run of 12 AWG copper at 120 V in a single-phase circuit produces about 3.18 V of drop, or 2.65% of system voltage. That result is below the 3% reference for this run, but it does not evaluate a feeder plus branch or certify an installation.
Temperature rating and insulation types
NEC ampacity tables assume specific conductor temperature ratings. Common insulation types:
- THHN: 90°C dry / 75°C wet; most common building wire in conduit.
- THWN-2: 90°C wet; suitable for underground and outdoor conduit.
- NM-B (Romex): 90°C conductors, but derated to 60°C in NM cable ampacity tables; used in residential walls.
When conduit is fully loaded (more than 3 current-carrying conductors), ampacity must be derated per NEC Table 310.15(B)(3)(a). High ambient temperatures (attics, boiler rooms) also require derating. The current values shown in the lookup table are simplified reference estimates, not NEC ampacity ratings; conductor material, insulation, installation method, ambient temperature, bundling, and local requirements all affect a safe design. Have a qualified electrician verify wiring for the actual installation.
Frequently asked questions
What is AWG?
AWG (American Wire Gauge) is a standardised wire gauge system used in North America. A lower AWG number means a thicker wire. 4/0 (0000) is the thickest standard gauge; 40 AWG is very fine.
What is the maximum current for a wire?
Maximum current depends on installation method. Chassis wiring (open air) allows higher current than wiring inside walls or conduit. Always derate for bundled cables or high ambient temperatures.
Related tools
- Ohm's Law CalculatorUse wire resistance to calculate voltage drop, current, or power loss.
- Voltage DividerModel meaningful wire resistance as part of a resistive network.
- Length ConverterConvert cable run length before estimating resistance and ampacity.
- Battery LifePair conductor sizing with the current draw used for runtime estimates.