Skip to content
Toolcroft

Science & Engineering

Wire Gauge Calculator - AWG Size Reference & Specs

Look up AWG wire gauge specifications: diameter, cross-section area, resistance per km, and maximum current ratings.

Your inputs are saved in this browser only. No data is ever sent to a server, and saved values won't be visible in other browsers or devices.
Diameter2.053 mm / 0.0808 in
Cross-section area3.309 mm²
Resistance (copper, 20°C)5.211 Ω/km (0.005211 Ω/m)
Max current - chassis / open air41 A
Max current - in-wall / conduit20 A
AWG ▲▼O (mm) ▲▼Area (mm2) ▲▼O/km ▲▼Max A (chassis) ▲▼
4/011.684107.20.1608380
3/010.40585.010.2028328
2/09.26667.430.2557283
1/08.25253.480.3224245
17.34842.410.4066211
26.54433.630.5127181
35.82726.670.6465158
45.18921.150.8152135
64.11513.31.296101
83.2648.3672.06173
102.5885.2613.27755
122.0533.3095.21141
141.6282.0818.28632
161.2911.30913.1722
181.0240.823120.9516
200.81280.518933.3111
220.64380.325553.467
240.51060.204784.223.5
260.40490.1288133.92.2
280.32110.081212.90.83
300.25460.0509338.60.52
320.20190.032538.30.32
340.16010.02018560.18
360.1270.0126713610.1
400.079870.0050134410.036

AWG wire gauge overview

The AWG (American Wire Gauge) system uses an inverse scale - lower numbers mean thicker wire. 4/0 (0000) is the largest common gauge; AWG 40 is fine enough for watch coils.

Choosing the right gauge

  • Match wire gauge to the maximum continuous current, not peak current.
  • Derate by 20–30% when bundling multiple conductors.
  • For long runs, consider voltage drop in addition to current capacity.

AWG to mm² conversion table

AWGmm²Typical use
18 AWG0.82 mm²Signal wiring, low-voltage lighting
14 AWG2.08 mm²General lighting circuits (15 A)
12 AWG3.31 mm²Standard outlets (20 A)
10 AWG5.26 mm²Dryers, EV charging (30 A)
6 AWG13.3 mm²Sub-panels, large appliances (55 A)

Voltage drop calculation

Excessive voltage drop causes motors to run hot and lights to dim. The NEC recommends voltage drop ≤3% on branch circuits and ≤5% total (feeder + branch). The formula is:

V_drop = I × R
where R = (resistivity × 2 × length) / cross-sectional area

Example: 20 A circuit, 50 feet of 12 AWG copper: R ≈ 0.16 Ω -> V_drop ≈ 3.2 V (2.7% on a 120 V circuit - within the 3% limit).

Temperature rating and insulation types

NEC ampacity tables assume specific conductor temperature ratings. Common insulation types:

  • THHN: 90°C dry / 75°C wet; most common building wire in conduit.
  • THWN-2: 90°C wet; suitable for underground and outdoor conduit.
  • NM-B (Romex): 90°C conductors, but derated to 60°C in NM cable ampacity tables; used in residential walls.

When conduit is fully loaded (more than 3 current-carrying conductors), ampacity must be derated per NEC Table 310.15(B)(3)(a). High ambient temperatures (attics, boiler rooms) also require derating.